The objective of this Standard Operating Procedure for Operation of Steam Boiler is to outline the steps and guidelines for the safe and efficient operation of a steam boiler to ensure reliable steam generation for various industrial processes.
SOP for Operation of Steam Boiler
- OBJECTIVE:
- To lay down the Procedure for Operation of Steam Boiler installed in utility area.
- SCOPE:
- This SOP is applicable to Operation of Steam Boiler installed in utility area .
- RESPONSIBILITY:
- Technician/ Operator of Engineering Department shall be responsible for proper execution of operation as per SOP for Operation of Steam Boiler.
- Engineering – Head shall be responsible for reviewing the SOP and for ensuring proper execution as per SOP for the Operation of Steam Boiler.
- ACCOUNTABILITY:
- Engineering – Head shall be accountable for proper implementation of the SOP for Operation of Steam Boiler.
- DEFINITIONS:
- Nil
- PROCEDURE:
- Pre Start up procedure:
- Pre-checkup to start the boiler.
- Check the water level in the feed water tank through level gauge.
- Check the Fuel level in the Diesel tank through level gauge.
- Check the HSD supply to the burner assembly.
- Check the pH of the feed water it should be between 8.5 to 9.5.
- Check the air vent valve of boiler, it should be open. Check Main steam valve it should be closed.
- Ensure that burner modulation switch is in “off” position.
- Check the water level in the gauge glass it should not be less than minimum level required.
- Open the main valves of HSD/ Furnace oil & feed water.
- Start Up procedure
- Switch ON the main panel of boiler.
- Switch the control supply to “on” mode.
- Switch ON the selected feed Water pump.
- Switch ON the burner switch.
- Switch ON the firing switch.
- After the burner switch ON, within 15 seconds firing will start inside the boiler.
- When steam starts comes from the air vent valve, close the air vent valve.
- When steam pressure reaches 5.0 kg/cm2 open the main steam valve.
- Check that all the steam traps are working properly.
- Check that boiler mounted safety is working properly like mowbray low safety in every shift.
- Put “on” the modulation switch.
- Ensure that blow down is effective.
- After startup of boiler, check the characteristic of the flame for proper functioning
- To Shut down the Boiler.
- Switch off the burner modulation switch.
- Turn off main fire/burner switch.
- When steam pressure reaches 3 kg/Cm2 close the main steam valve while slightly opening air vent valve.
- Open the air vent valve.
- Feed water pump should be switched “On” to make up the water.
- When steam pressure comes at 0 kg/cm2– switch off the feed water pump.
- Switch Off the main Panel of boiler.
- Leave the air vent valve open.
- Record the detail of operation after every 02 hrs from start of the boiler as per Format No. SOP/EN/XXXYYY.
- Record the detail of total running hrs, steam flow meter reading, steam consumption, HSD dip should be taken after every 24 hrs.
- ABBREVIATIONS
- HSD : High Speed Diesel
- REFERENCES
- Operational & Maintenance Manual of Steam Boiler.
- DISTRIBUTION LIST
- SOP shall be distributed to following departments Quality Assurance, Engineering as per user request.
- ANNEXURES
- Log Book for the operation of Steam Boiler : SOP/EN/XXXYYY
- DAILY LOG-SHEET FOR STEAM BOILER CAPACITY 1000Kg/Hrs.
- Log Book for the operation of Steam Boiler : SOP/EN/XXXYYY
- DATE:………………. EQUIPMENT ID: ……………………
TIME | STEAM PRESSURE (kg/cm2) | FEED WATER PRESSURE (kg/cm2) | FUEL OIL PRESSURE (kg/cm2) | FEED WATER TEMP. | BLOW DOWN PH (in PPM) | FEED WATER PH (in PPM) | BLOW DOWN TDS (in PPM) | FEED WATER TDS (in PPM) | BLOW DOWN HARDNESS (in PPM) | FEED WATER HARDNESS (in PPM) | FLUE GAS TEMP. | HSD ADD. | OPERATOR NAME | OPERATOR SIGN | REMARKS |
FUEL CONSUMPTION-
STEAM FLOW METER READING – STEAM CONSUMPTION-
HSD DIP- CHECKED BY : ………………..
DAILY LOG-SHEET FOR STEAM BOILER CAPACITY 1000Kg/Hrs
DATE:………………. EQUIPMENT ID: ……………………
TIME | STEAM PRESSURE (kg/cm2) | FEED WATER PRESSURE (kg/cm2) | FUEL OIL PRESSURE (kg/cm2) | FEED WATER TEMP. | FLUE GAS TEMP. | HSD ADD. | OPERATOR NAME | OPERATOR SIGN | REMARKS |
FUEL CONSUMPTION-
STEAM FLOW METER READING –
STEAM CONSUMPTION-
HSD DIP-
STEAM FUEL RATIO-
BOILER FEED WATER PH (in PPM)-
BOILER BLOW DOWN PH (in PPM)-
BOILER FEED WATER TDS (in PPM)-
BOILER BLOW DOWN TDS (in PPM)-
CHECKED BY : ………………..