Specification of Fire Fighting Sprinkler System

Fire fighting sprinkler systems are an essential component of building safety, designed to suppress and control fires automatically. These systems operate by detecting heat from a fire and discharging water over the affected area, minimizing damage and preventing fire spread. Below are the key specifications of fire fighting sprinkler systems, covering their types, components, design criteria, and performance standards.

Types of Fire Sprinkler Systems

Fire sprinkler systems are categorized based on their design and application:

  • Wet Pipe System:          Contains water in the pipes at all times, releasing it immediately when a sprinkler head is activated. Ideal for buildings with a controlled climate.
  • Dry Pipe System:          Contains pressurized air or nitrogen in the pipes, which is expelled before water is released. Suitable for cold environments where freezing is a concern.
  • Deluge System:  Uses open sprinkler heads connected to a water supply, activated by a separate detection system. Used in high-hazard areas where rapid fire spread is a risk.
  • Pre-action System:         Requires two triggers (detection system and sprinkler activation) before releasing water. Commonly used in data centers and museums to prevent accidental discharge.
Fire fighting sprinkler system

Components of a Fire Fighting Sprinkler System

A fire sprinkler system consists of multiple critical components:

Sprinkler Heads:          Heat-sensitive devices that discharge water upon reaching a set temperature.

Piping Network:         Carries water from the supply to the sprinkler heads. Can be steel, copper, or CPVC.

Control Valves: Regulate water flow and enable system maintenance. Includes main shut-off valves and alarm valves.

Water Supply:  Can be from a municipal connection, fire pump, or dedicated storage tanks.

Fire Pump:       Boosts water pressure for large or high-rise buildings.

Alarm System:  Activates when a sprinkler discharges, alerting occupants and emergency responders.

Design Criteria and Standards

The performance of a fire sprinkler system depends on its design parameters. Some key factors include:

Coverage Area Typically 130-225 square feet per sprinkler head, depending on hazard level.

Operating Temperature: 135°F to 500°F (57°C to 260°C), varying based on sprinkler type.

Water Flow Rate: Minimum 0.1 to 0.6 gallons per minute (GPM) per square foot, depending on occupancy hazard classification.

Pipe Pressure: Typically ranges from 7 psi to 60 psi, depending on system size and water source.

Response Time Index (RTI):     Measured in (m−1/2s−1/2), categorizing standard response (>80), fast response (50-80), and quick response (<50).

Hazard Classifications and Required Water Density

The water discharge rate depends on the hazard level of the area being protected:

Hazard ClassificationExample AreasWater Density (GPM/sq. ft)
Light HazardOffices, Schools, Hospitals0.10-0.15
Ordinary Hazard (Group 1)Retail Stores, Parking Garages0.15-0.20
Ordinary Hazard (Group 2)Factories, Warehouses0.20-0.30
Extra Hazard (Group 1)Chemical Plants, Printing Facilities0.30-0.40
Extra Hazard (Group 2)Aircraft Hangars, Power Plants0.40-0.60

How Fire Sprinkler Heads Work

All fire sprinkler heads share common components:

  • Sealing Assembly: Prevents water from escaping until activation.
  • Heat-Sensitive Element: Triggers the sprinkler at a specific temperature.
  • Deflector: Directs water to cover the intended area.
  • Frame: Holds all components together.

Sprinklers activate when their heat-sensitive element—either a glass bulb or a fusible link—reacts to heat. Glass bulbs contain a glycerin-based liquid that expands and shatters the bulb at a designated temperature (e.g., 155°F or 200°F). Fusible link sprinklers use a metal alloy that melts under heat, allowing water to flow.

Sprinklers come in two standard sizes:

  • 1/2″ (12.7 mm): Common in offices, schools, and hotels.
  • 3/4″ (19.3 mm): Used in high-risk environments requiring greater water flow.
Fire fighting sprinkler system

Fire Sprinkler Bulb Temperature Ratings

Sprinklers activate at specific temperature thresholds, identified by color-coded bulbs or paint markings:

Bulb ColorActivation Temperature (F°/C°)
Orange135°F (57°C)
Red155°F (68°C)
Yellow175°F (79°C)
Green200°F (93°C)
Blue286°F (141°C)
Purple360°F (182°C)
STRUCTURAL STEEL WORK – FABRICATION AND ERECTION SCOPE:

This specification covers the supply, fabrication, transportation to Site and erection on prepared foundations, structural steel Work consisting of columns, beams, flooring, hand railing etc. for pipe racks, Equipment, supporting structures, platforms, etc.

APPLICABLE CODES AND SPECIFICATIONS:

The following specification, standards and codes shall be part of this specification. All standards, specifications, codes of practice referred to herein shall be the latest editions including all applicable official amendments and revisions.

Standard Response vs. Quick Response Sprinklers

  • Quick Response (QR): Used in hotels, dormitories, and public spaces. Features a smaller (3mm) glass bulb for faster activation, giving occupants more time to escape.
  • Standard Response (SR): Found in commercial and industrial settings, prioritizing building protection over human evacuation.

K-Factor and Water Discharge Rate

The K-factor determines the water flow rate. A higher K-factor allows for greater water discharge at a given pressure.

K-FactorTypical Use Case
5.6KStandard environments (offices, apartments)
8.0KHigh-risk environments (garages, warehouses)
11.2K+Extra hazard locations (industrial facilities)

Types of Fire Sprinkler Heads

1. Pendent Type Sprinklers

  • Overview: Hangs from ceiling pipes and sprays water in a dome-shaped pattern.
  • Common Uses: Offices, schools, hotels, residential buildings.
  • Notable Models: Viking VK3021, Tyco TY323, Victaulic V2708.
  • Special Features:
    • Some models include corrosion-resistant coatings for humid environments.
    • Can be installed with escutcheons for aesthetic appeal.

2. Upright Sprinklers

  • Overview: Installed with the deflector facing upward, designed for areas where obstructions prevent pendent sprinkler use.
  • Common Uses: Warehouses, industrial spaces, open-ceiling structures.
  • Notable Models: Viking VK2001, Victaulic V3402.
  • Special Features:
    • Suitable for dry-pipe systems in freezing environments.
    • Some models include corrosion-resistant coatings.

3. Sidewall Sprinklers

  • Overview: Installed along walls or under beams where ceiling piping isn’t feasible.
  • Common Uses: Hallways, hotel rooms, restaurants.
  • Notable Models: Tyco TY3331, Viking VK305, Victaulic V27.
  • Special Features: Horizontal sidewall sprinklers require smooth ceilings for optimal operation. Available with protective coatings against corrosion.

4. Concealed Sprinklers

  • Overview: Installed behind a decorative cover plate that detaches when heat reaches a certain level.
  • Common Uses: Hotels, offices, luxury apartments.
  • Notable Models: Victaulic V3802, Senju SS2521, Tyco RFII.
  • Special Features:
    • Cover plates are customizable to match interior aesthetics.
    • Requires replacement of the cover plate after activation.

MATERIALS:

  • IS 102                   Ready Mixed Paint, Brushing, Red Lead, non-setting, Priming.
  • IS 449                  The Use of Structural Steel in Building.
  • IS 639                  Covered Electrodes for the Manual Metal Arc Welding of Mild Steel and Medium Tensile Steel.
  • IS 800                  Codes of Practice for Use of Structural Steel in General Building Construction.
  • IS 801                  Code of Practice for Use of Cold Formed Light Gauge Steel Structural Members in General Building Construction.
  • IS 806                   Code of Practice for Use of Steel Tubes in General Building Construction.
  • IS 808                   Rolled Steel Beam, Channel and Angle Sections
  • IS 814                   Specifications for Covered Electrodes for Metal Arc Welding for Mild Steel.
  • IS 816                  Code of Practice for use of Metal Arc Welding for General Construction.
  • IS 817                  Code of Practice for Training and Testing of Metal Arc Welders.
  • IS 823                  Code of Procedure for Manual Metal Arc Welding of Mild Steel.
  • IS 871                  Code of Practice for Structural Safety of Building – Loading Standards.
  • IS 919                  Recommendations for Limits and Fits for Engineering.
  • IS 961                  Structural Steel (High Tensile).
  • IS 1083                Precision Hexagonal Bolts, Screws and Nuts (BSW & BSF Threads).
  • IS 1148                 Rivet Bars for Structural Purposes.
  • IS 1149                 High Tensile Rivet Bars for Structural Purposes.
  • IS 1181                Qualifying Tests for Metal Arc Welders (engaged in welding structures other than pipes).
  • IS 1182                 Recommended Practice for Radiographic examination of Fusion – Welded Butt Joins in Steel Plates.
  • IS 1334                    Code of Practice for Magnetic Particle Flaw Detection of Welds
  • IS 1363                 Black Hexagonal Bolts, Nuts and Lock Nuts (diameter 6 to 39 mm) and Black Hexagonal Screws (diameter 6 to 24 mm)
  • IS 1364                 Precision and Semi-Precision Hexagonal Bolts, Screws, Nuts and Lock Nuts (diameter 6 to 39 mm).
  • IS 1367                 Technical Supply Conditions for Threaded Fasteners.
  • IS 1477                Code of Practice for Painting of Ferrous Metals in Buildings and Allied Finishes.
  • IS 1812                Specification for Rolling and Cutting Tolerances for Hot Rolled Steel Products.
  • IS 1893                  Recommendations for Earthquake Resistant Design of Structures.
  • IS 1977                   Structural Steel (Ordinary Quality)
  • IS 2016                   Plain Washers.
  • IS 2062                   Structural Steel (Fusion Welding Quality)
  • IS 2074                   Ready Mixed Paint, Red Oxide Zinc Chrome and Priming.
  • IS 2191                   Code of Practice for Radiographic Testing.
  • IS 3139                   High Strength Friction Grip Bolts for Structural Engineering.
  • IS 3613                   Acceptance Tests for Wire Flux Combinations for Submerged-Arc Welding.
  • IS 3618                    Code of Practice for Liquid Penetrant Flaw Detection.
  • IS 3717                    High Tensile Friction Grip Fasteners for Structural Engineering Purposes.
  • IS 4000                    Code of Practice for Assembly of Structural Joints using High Tensile Friction Grip Fasteners.
  • IS 4313                    Recommendations for Submerged Arc Welding of Mild Steel and Low Alloy Steels.
  • IS 7201                     Safety code of Erection of Structural Steel Work.
  • IS 7211                      Tolerances for Fabrication of Steel Structures.
  • ASTM A6              General Requirements for Delivery of Rolled Steel Plates, Shapes, Sheet Pilling and Bars for        Structural Use.
  • ASTM A321           High Strength Steel Bolts for Structural Joints.
  • ASTM E94           Recommended Practice for Radiographic Testing.
  • ASTM E109           Dry Powder Magnetic Particle Inspection.
  • ASTM E138           Wet Magnetic Particle Inspection.
  • ASTM E161              Liquid Penetrant Inspection.
  • AWS:                      Standard Code of Welding in Building Construction.
  • AWS A-1.1      Specification for Mild Steel Covered Arc Welding Electrodes.
  • AWS A-1.17                     Specification for Bare Mild Steel Electrodes and Fluxes for Submerged Arc Welding.
  • AISC: Specification for the Design, Fabrication and Erection of Structural Steel for Buildings.
  • BS 3294: The Use of High Strength Friction Grip Bolts in Structural Steel Work.
  • Research Council on Riveted and Bolted Structural Joints – Specification for Structural Joints using ASTM A321 or A 490 Bolts.

Fire Protection System

SCOPE

This specification covers the design, engineering, supply, fabrication, transportation, installation, testing & commissioning of fire protection system and preparation necessary drawings and documents and obtain necessary statutory approvals on drawings and constructed firefighting systems.

M/s. Flair Pharma is intended to set a formulation facility, desirous to have a fire protection system implemented as per the prevailing rules and regulations of the land. The designer has taken paramount interest in seeing that the unit is protected properly. The system will be designed as per the recommendations given by the consultant, and as per local statutory norms.

This plant given as moderate / ordinary hazard for entire plant following are the system proposed for this plant -:

a)  Fire Sprinkler System

REFERENCES AND CONSIDERATIONS:

The following are the references and assumptions considered for making this document:

  • The user requirement specifications for this facility are given as per the details provided by the Consultants.

LIST OF RELEVANT STANDARDS: –

Sr. No.Standard No.Description
1.NBC 2016Part 4 – Fire & Life Safety
2.IS:388Hose Tubing
3.IS:554Dimensions for pipe threads where pressure tight joints are required on the threads
4.IS: 636Flexible Fire Fighting Delivery Hose
  5.IS:778Copper alloy gate, globe and check valves for water work Purposes.
  6.IS:780Sluice valves for water-works purposes (50mm to 300mm)
  7.IS:901Couplings, double male and double females, instantaneous Pattern for Fire Fighting
8.IS:903Fire hose delivery couplings, branch pipe, nozzles and Nozzle spanner
9.IS:940Portable fire extinguishers water type (Gas Pressure)
10.IS:1239Mild steel tubes, tabular and other wrought steel fittings (Part I & II)
11.IS:3589Mild Steel Pipes of sizes above 150mm dia.
12.IS: 3844Internal Fire Hydrant
13.IS:3876Swinging type wall mounted hose reel with drum
14.IS:4038Specification for foot valves for water works purposes
15.IS: 5290Specification for Landing Valve
16.IS:5312Non-return valve
17.IS:8442Water monitor
18.IS:10001Diesel Engine
19.IS: 10221Wrapping and Coating of Mild Steel Pipes
20.IS: 15105Sprinkler System
21.IS: 15325Water Spray System
22.Fire ManualFire Protection Manual TAC

Specifications of the Different Equipment’s of the Sprinkler System

OS & Y Valve
  • Name   :           OS & Y Valve Flange End 150#
  • Tag No.   :           *
  • Type     :           OS & Y Valve, Indian Standard PN 1.6 (16 KG/SQ.CM)
  • Design Standard            :           •
  • Dimension Standard      :           ANSI B16.1
  • Flange Drilling  :           ANSI B16.5
  • Rating  :           150#
  • Make    :           As mentioned in BOQ
  • Model No.        :           *
  • Service :           Water
  • Op. Temperature – Min/Max (°C)          :           Ambient
  • Op. Pressure – Min/Max (kg/cm²(g))      :           *
  • Rated Pressure of Valve, minimum required – (kg/cm²(g))           :            16
  • End      :           Flanged RF

Material of Construction OS & Y Valve                     

  •             Body    :           *
  •             Bonnet :           *
  •             Disc     :           *
  •             Stem     :           *
  •             Gland Flange    :           *
  •             Gland Packing  :           *
  •             Gasket  :           *
  •             Hand wheel      :           *
  •             Hardware          :           *
Non Return Valve
  • Name   :           Check Valve Flange End 150#
  • Tag No.            :           *
  • Type     :           *
  • Design Standard            :           *
  • Dimension Standard      :           ANSI B16.5
  • Make    :           As mentioned in BOQ
  • Model No.        :           *
  • Service :           Water
  • Op. Temperature – Min/Max (°C)          :           Ambient
  • Op. Pressure – Min/Max (kg/cm²(g))      :           -1/10
  • Rated Pressure of Valve, minimum required – (kg/cm²(g))           :           16
  • Test Pressure as per API 6D       :          
  •             Body –Hydraulic (kg/cm²(g))     :           *
  •             Seat –Hydraulic (kg/cm²(g))       :           *
  • End      :           *
  • Flange rating     :           ANSI B16.5,ASA 150#
  • Material of Construction                    
  •             Body    :           *
  •             Seating :           *
  •             Disc     :           *
  •             Hinge   :           *
  •             Trim     :           *
  •             Sealing Ring     :           *
  •             O ring   :           *
Air Release Valve
  • Name   :           Stainless Steel, Air Release valve, Flange End 150#
  • Tag No.            :           *
  • Type     :           Single ball type
  • Make    :           As mentioned in BOQ
  • Model No.        :           *
  • Service :           Water
  • Vacuum            :           Full
  • Vapour :           N.A.
  • Op. Temperature – Min/Max (°C)          :           Ambient
  • Op. Pressure – Min/Max (kg/cm²(g))      :           *
  • Rated Pressure of Valve, minimum required – (kg/cm²(g))           :           *
  • End      :           1″ BSP ( M ) threaded
  • Material of Construction                    
  •             Body    :           *
  •             Seating :           *
  •             Ball      :           *
Butterfly Valve
  • Name   :           Wafer Type 150#
  • Tag No.            :           *
  • Type     :           Up to 150 NB lever operated and
  • Above 150 NB Gear operated with tamper switch
  • Design Standard            :           *
  • Dimension Standard      :           *
  • Flange Drilling  :           ANSI B16.5
  • Rating  :           150#
  • Make    :           As mentioned in BOQ
  • Model No.        :           *
  • Service :           Water
  • Vacuum            :           Full
  • Vapour :           N.A.
  • Op. Temperature – Min/Max (°C)          :           Ambient
  • Op. Pressure – Min/Max (kg/cm²(g))      :           *
  • Test Pressure as per API 598      :          

            Body –Hydraulic (kg/cm²(g))     :           31

            Seat –Hydraulic (kg/cm²(g))       :           23

            Seat – Pneumatic (kg/cm²(g))     :           7

End      :           Flanged RF

Material of Construction                    

  •             Body    :           *
  •             Bonnet :           *
  •             Disc     :           *
  •             Stem     :           *
  •             Gland Flange    :           *
  •             Gland Packing  :           *
  •             Gasket  :           *
  •             Lever    :           *
  •             Hardware          :           *
Pressure Gauge

Make    :           As mentioned in List of Make

General           

            Type     :           Bourdon Sensing Pressure Gauge, Glycerin Filled

            Dial Size           :           150 mm ( 6”)

            Case     :           Weatherproof IP-65, Die cast Aluminum Material

            Glass    :           Toughened , Shatterproof

            Pointer  :           Micrometer type , Aluminum Black Colored

            Zero Adjustment           :           Required externally

            Accuracy          :           ± 1% of FSD

            Dial      :           Single Black marking on white background

            Bezel Ring        :           Screwed type/Bayonet Type

            Process Connections     :           1/ 2″ BSPT (M)

            Pressure Range :           0 to 16 Kg/cm2 (g)

            Over Range Protection   :           130 % Of Range span

            Blow Out Disc  :           Required ( Neoprene )

Material                       

            Bourdon           :           SS 316

            Socket  :           SS 316

            Movement        :           SS 304

            Case     :           Die Cast Aluminum

            Bezel Ring        :           Die Cast Aluminum

Accessories      :           For requirement refer attached annexure

            Syphon :           ½” BSPT (F) x ½” BSPT (M), Pig Tail, SS 304

            Snubber            :           ½” BSPT (M) x ½” BSPT (F), SS 304

Pressure Switch

Make    :           As mentioned in List of Make

SWITCH                     

            Type     :           Diaphragm / Bourdon Sensing Pressure Switch

            Range   :           0-20 Kg/cm2(g)

            Dead Band        :           ± 0.5% Adjustable.

            Contact :           SPDT Snap acting micro switch

            Contact rating   :           2A, at 24VDC

            Process Connection       :           1/2” BSPT

            Cable Entry       :           ½” NPT(F)

            Accuracy          :           ± 0.5% of RANGE.

            Housing            :           Whether proof IP 65

            Service conditions         :           Water

MATERIAL                

            Housing            :           Die Cast Aluminum, Epoxy Painted

            Diaphragm/ Bourdon     :           SS 316

            Wetted parts     :           SS 316

            Fill fluid           :           *

Y Strainer

General           

  •             Type     :           Y
  •             PN Rating         :           16 to 25
  •             Size      :           As per BOQ
    • MATERIAL                
  •             Housing            :           Cast Iron
  •             Filter Material   :           SS 304 with 5mm mesh
Basket Type Strainer

General           

  •             Type     :           Basket/Pot type
  •             PN Rating         :           16
  •             Size      :           200 mm and above

MATERIAL                

  •             Housing            :           Cast Iron / (MS Fabricated for 300mm and above)
  •             Filter Material   :           SS 304
  •             Screen Size                   0.5mm
Flowmeter:
  •             Make    :           Electromagnetic type
  •             MOC    :           AISI 304
  •             Temperature Rating       :           Up to 250 deg C
  •             Measuring Range          :           1 to 700 m3/hr.
  •             Connection       :           Flange ASA/BS
  •             Rotor Chamber :           AISI 304
  •             Turbine Rotor   :           AISI 304
  •             Shaft    :           Tungsten Carbide
  •             Washer :           PTFE
  •             Bearing Bush    :           Tungsten Carbide            
  • Magnetic pick up coil sensor      :           SS
Pressure Relief Valve

General           

  •             Type     :           Pilot & Self Actuated
  •             External Body   :           Cast Steel to ASTM A 216, Grade 65-45-12
  •             Seat      :           CF8M ASTM A 351
  •             Internal Body    :           SS
  •             Size      :           As per BOQ
  •            Finish               Hot-dipped, Galvanized conforming to ASTM A153
Pressure Reducing Valve

General           

  •             Type     :           Pilot & Self Actuated
  •             External Body   :           Ductile Iron ASTM A536
  •             Seat      :           Bronze ASTM B 176
  •             Disc     :           Buna-N Rubber
  •             Stem     :           Stainless Steel
  •             Spring  :           Stainless Steel
  •             Flanges :           CLASS 300 – ANSI B16.42
  •             Size      :           As per BOQ
  • Finish   :           Epoxy Coated, FDA Approved
SPRINKLER & ACCESSORIES

SPRINKLER

  • Make    :           Refer Tender BOQ       
  • Approvals         :           UL or FM        
  • Max Working Pressure  :           175 psi (12.1 bar)         
  • K – factor         :           K 80 / K 115    
  • Temperature Rating       :           68°C   
  • Finishes            :           Chrome Plated 
  • Frame   :           BRONZE        
  • BULB  :           GLASS
  • Deflector          :           BRONZE        
  • Type     :           Upright, Pendent & Concealed
Alarm valve
  • Make                Refer Tender BOQ       
  • Application       :           Positive Operation For Alarm Valve      
  • Type     :           Single acting    
  • Fluid    :           Fire water        
  • Size      :           150NB
  • Maximum Pressure       :           17.5 bar           
  • Material of construction                        
  • Body    :           DI       
  • Trim     :           Galvanised Fittings with Brass Valve    
  • Washer :           Rubber
  • End Connection :           Flanged
  • Certificate         :           All Material to be supplied should be new and with necessary approval certificates along with Manufacturers Test Certificates duly signed and stamped, no material supplied will be acceptable without these documents.
Ducting work

Frequently Asked Questions

What are the technical specifications of a fire hydrant?

Answer: Fire hydrants are designed to provide water supply for firefighting. Their specifications include:

Type: Wet barrel or dry barrel

Outlet Connections: 2.5-inch (65 mm) and 4.5-inch (115 mm) standard

Operating Pressure: 1.4 to 3.5 bar (20 to 50 psi)

Flow Rate: 1,000–2,500 GPM (gallons per minute)

Material: Cast iron or ductile iron

Valve Type: Compression, slide gate, or ball type

Coating: Corrosion-resistant epoxy coatings

What are the NFPA 13 sprinkler clearance requirements?

Answer: Ceiling Clearance: Minimum 36 inches (914 mm) for storage exceeding 12 feet

Sidewall Sprinkler Clearance: At least 4 inches (102 mm) from walls

Obstruction Requirements: No blockage within 18 inches around the sprinkler

Fire Damper
What are the 4 types of sprinkler systems?

Answer: Wet Pipe System: Pipes contain water at all times, activated immediately.

Dry Pipe System: Pipes contain pressurized air, releasing water upon activation.

Pre-action System: A two-step activation system preventing accidental discharge.

Deluge System: All sprinklers discharge water simultaneously upon activation.

What is the NFPA standard for fire hydrant system?

Answer: NFPA 24: Standard for the installation of private fire service mains.

NFPA 291: Fire flow testing and marking of hydrants.

What is the pressure of a sprinkler pump in KG?

Answer: Typically 7–10 kg/cm² (100–140 psi), depending on system requirements.

What is the maximum distance of a fire hydrant?

Answer: NFPA 1 & NFPA 24: 250 ft (76 m) maximum distance between hydrants.

For buildings: 50–100 ft (15–30 m) from a hydrant.

What are the NFPA hydrant ratings?

Answer:  Red: Below 500 GPM

Orange: 500–999 GPM

Green: 1,000–1,499 GPM

Blue: 1,500 GPM or more

What is the best type of sprinkler?

Answer: Pendent Sprinklers: Best for commercial ceilings.

Upright Sprinklers: Ideal for industrial areas.

Sidewall Sprinklers: Best for corridors and small rooms.

What size are fire sprinkler heads?

Answer: Standard Size: ½-inch (12.7 mm) or ¾-inch (19 mm)

Flow Rates: Varies between 15-25 GPM

What is a Category 4 sprinkler system?

Answer: A high-risk system for hazardous materials and industrial facilities.

What is the 18 sprinkler rule?

Answer: NFPA 13 requirement: Maintain an 18-inch clearance between sprinkler heads and storage items.

What is the distance between sprinklers?

Answer: Standard Spacing: 10 to 15 ft (3–4.5 m) apart.

Maximum Distance: 15 ft (4.5 m).

What NFPA standard applies to fire sprinklers?

Answer: NFPA 13: Standard for installation of sprinkler systems.

What is the color code of a fire hydrant?

Answer: NFPA 291:

Red: < 500 GPM

Orange: 500–999 GPM

Green: 1,000–1,499 GPM

Blue: ≥ 1,500 GPM

What is NFPA fire rating?

Answer: Fire rating is based on NFPA 704 (Hazardous Materials Identification):

0-4 scale for health, flammability, and reactivity.

What is the MS standard for hydrants?

Answer: MS 1397: Malaysian Standard for fire hydrants.

How is NFPA rating calculated?

Answer: NFPA 704 Diamond System:

Blue: Health (0–4)

Red: Flammability (0–4)

Yellow: Reactivity (0–4)

White: Special hazards

What is SDS?

Answer: Safety Data Sheet (SDS): Document detailing hazardous substances and safety measures.

What is a good fire rating?

Answer: Fire Resistance Rating (FRR):

1-hour, 2-hour, 3-hour, or 4-hour fire resistance levels.

What class of fire extinguisher?

Answer: Class A: Combustibles (wood, paper)

Class B: Flammable liquids

Class C: Electrical fires

Class D: Metal fires

Class K: Cooking oils

What paint is used on fire hydrants?

Answer: Enamel-based, UV-resistant epoxy paint for corrosion protection.

How much water is in a fire hydrant?

Answer: Depends on local pressure; average hydrants provide 500–2,500 GPM.

Technical Specification-Fire fighting system reference doc

Leave a Comment